| Features | Specifications | DataSheet |
|
|
The 4150 is a new generation of "smart" Remote Terminal
Unit (RTU)
that combines the functions of a distributed Remote
I/O Module, a Datalogger and an Alarm Dialer at a significantly
lower cost than integrating separate devices. Windows based
"Toolbox" software makes simple, either locally, or
over the communications link. The Digital Inputs support AC or DC
signals and are individually configurable for input voltage and
filtering. The RTU monitors the ON transitions and runtime for
each Digital Input. The Analog Inputs are individually
configurable for voltage or current operation. The first four
Digital and Analog Inputs can totalize (for flow or wattage)
scaled to engineering units. The Data logging feature records all
digital states, analog levels, totalizers and runtime, with time
and date stamping at a user defined rate. With the internal
telephone modem option installed, any Digital Input, High/Low
Analog level or totalizer rate can initiate Alarm Dialing from
one of four telephone number lists, optionally with voice
annunciation. Alarms are acknowledged by touchtone telephone or
local input. An optional built-in Operator Interface provides a
display of I/O states and levels, totalized counts, and local
alarm acknowledgment.
| Digital Inputs | 12 (3 groups of 4 inputs), 2,000-volt optical isolation |
| Digital Input Voltages | 0 to 30Vac/Vdc, 120 Vac/Vdc, user configurable |
| Digital Input Pulse Rate/Runtime | 0 to 5KHz (first 4 inputs only), up to 65,535 minutes each |
| Digital Outputs | 6, Form A (NO) Relay Contacts, 2,000-volt isolation |
| Digital Output Switching Level | 0 to 120Vac/Vdc, 3A maximum |
| Analog Inputs | 8, 12-bit, (1 part in 4096), 2,000 volt optical isolation, 5Vdc or 20mA DC, user configurable |
| Analog Outputs (option) | 2, 10-bit, 20mA,, user configurable, 2,000 volt optical isolation, external power 12 to 30Vdc, 100mA max. |
| Standard Communications | RS-232 |
| Communications Protocol/Rate | Modbus RTU, up to 9600 baud |
| Data logging | 914 records / 3,986 records max., 1 record every 1 to 255 minutes (4.25 hours) |
| Voice Alarming (option) | User recorded messages for 36 alarm conditions (90 seconds total) |
| Operator Interface (option) | 2 lines of 12 characters (24 characters total) LED, Dot matrix alphanumeric green display, 3 key keypad (scroll up, scroll down, alarm ACK) |
| Internal Telephone Modem (option) | PC/"Hayes" compatible, up to 9600 baud |
| Internal Radio Modem (option) | RMX-2400 compatible, up to 2400 baud, Audio/PTT interface |
| Power | 10 to 30Vdc (10 to 16Vdc with internal SS Radio), 2.5 Watts typical, 4 Watts maximum (modem/display options) |
| Temperature | -40°C to 75°C Operating, -40°C to 100°C Storage |
| Humidity | 10 to 90%, non-condensing |
| Dimensions | 75 x 110 x 149 mm 2.95 x 4.33 x 5.85 inches |
| Model # | Description |
| 41-4150 | 4150 with 8 AI, 12 DI and 6 DO |
| 41-4150-AO | Add 2 10-bit 20 mA AO |
| 41-4150-LOG | Add extended Data Logging capacity |
| 41-4150-SSR900 | Add internal 900 MHz Spread Spectrum Radio |
| 41-4150-SSR2400 | Add internal 2.4 GHz Spread Spectrum Radio |
| 41-4150-TBX | Windows "Toolbox" configuration software & cable for PC comm. |
|
|
|
|
|
|
* PDF format -- requires Adobe Acrobat Reader 4.0 or newer.