4150 RTU

Remote Terminal Unit



Features Specifications DataSheet


Features

  • Easy to use RTU with built-in data logging & alarm dialing
  • Ideal for small well sites, tank sites & lift stations
  • 8 12-bit Analog Inputs; 5Vdc or 20mA
  • 2 10-bit Analog Outputs, 20mA (option)
  • 12 Isolated Digital Inputs; 12/24/120 volts AC & DC
  • 6 Digital Outputs
  • "Plug-and-play" compatible with popular SCADA/DCS software, PLCs & Process Controllers
  • Easy installation & maintenance with "Point & Click" Windows based Toolbox software
  • Simple I/O expansion through the built-in RS-232 port
  • Works reliably over radio, leased lines & dial-up or cellular telephone
  • Compact package, DIN rail mounting for lower panel costs
  • Wide temperature range - eliminates fans & heaters in outdoor enclosures
  • Ideal for solar, mobile & battery operation - low current DC power
  • Engineered for safety and reliability with fault tolerant I/O, isolation, error checking & dual watchdog timers to protect personnel & equipment
  • Pulse & analog flow rate & totalization with scaling
  • Built-in "Store-and-Forward" messaging
  • Live datalog download & configuration upload over data link
  • Internal Spread Spectrum Radio (option)
  • Alphanumeric LCD Display/Keypad Operator Interface (option)
  • Internal Telephone Modem (option)
  • "Natural Voice" alarm annunciation (option)
  • Easily customized labeling for unique OEM identity

The 4150 is a new generation of "smart" Remote Terminal Unit (RTU) that combines the functions of a distributed Remote I/O Module, a Datalogger and an Alarm Dialer at a significantly lower cost than integrating separate devices. Windows based "Toolbox" software makes simple, either locally, or over the communications link. The Digital Inputs support AC or DC signals and are individually configurable for input voltage and filtering. The RTU monitors the ON transitions and runtime for each Digital Input. The Analog Inputs are individually configurable for voltage or current operation. The first four Digital and Analog Inputs can totalize (for flow or wattage) scaled to engineering units. The Data logging feature records all digital states, analog levels, totalizers and runtime, with time and date stamping at a user defined rate. With the internal telephone modem option installed, any Digital Input, High/Low Analog level or totalizer rate can initiate Alarm Dialing from one of four telephone number lists, optionally with voice annunciation. Alarms are acknowledged by touchtone telephone or local input. An optional built-in Operator Interface provides a display of I/O states and levels, totalized counts, and local alarm acknowledgment.


Specifications

Digital Inputs 12 (3 groups of 4 inputs), 2,000-volt optical isolation
Digital Input Voltages 0 to 30Vac/Vdc, 120 Vac/Vdc, user configurable
Digital Input Pulse Rate/Runtime 0 to 5KHz (first 4 inputs only), up to 65,535 minutes each
Digital Outputs 6, Form A (NO) Relay Contacts, 2,000-volt isolation
Digital Output Switching Level 0 to 120Vac/Vdc, 3A maximum
Analog Inputs 8, 12-bit, (1 part in 4096), 2,000 volt optical isolation, 5Vdc or 20mA DC, user configurable
Analog Outputs (option) 2, 10-bit, 20mA,, user configurable, 2,000 volt optical isolation, external power 12 to 30Vdc, 100mA max.
Standard Communications RS-232
Communications Protocol/Rate Modbus RTU, up to 9600 baud
Data logging 914 records / 3,986 records max., 1 record every 1 to 255 minutes (4.25 hours)
Voice Alarming (option) User recorded messages for 36 alarm conditions (90 seconds total)
Operator Interface (option) 2 lines of 12 characters (24 characters total) LED, Dot matrix alphanumeric green display, 3 key keypad (scroll up, scroll down, alarm ACK)
Internal Telephone Modem (option) PC/"Hayes" compatible, up to 9600 baud
Internal Radio Modem (option) RMX-2400 compatible, up to 2400 baud, Audio/PTT interface
Power 10 to 30Vdc (10 to 16Vdc with internal SS Radio), 2.5 Watts typical, 4 Watts maximum (modem/display options)
Temperature -40°C to 75°C Operating, -40°C to 100°C Storage
Humidity 10 to 90%, non-condensing
Dimensions 75 x 110 x 149 mm
2.95 x 4.33 x 5.85 inches



Ordering Information

Model # Description
41-4150 4150 with 8 AI, 12 DI and 6 DO
41-4150-AO Add 2 10-bit 20 mA AO
41-4150-LOG Add extended Data Logging capacity
41-4150-SSR900 Add internal 900 MHz Spread Spectrum Radio
41-4150-SSR2400 Add internal 2.4 GHz Spread Spectrum Radio
41-4150-TBX Windows "Toolbox" configuration software & cable for PC comm.