| Features | Specifications | DataSheet |
Features
The UPS Option adds...
|
|
The ICL-4003 is a reliable industrial power supply, featuring extended operating temperature capability and DIN rail mounting. It provides 36 watts of unregulated and regulated power, and with the Uninterruptible Power Supply (UPS) option, battery-backed power, for ICL "PC in a Brick" Controllers, "RTU in a Brick" Remote Telemetry Units, as well as radios, sensors and other DC powered control hardware.
Without the UPS option, the supply provides unregulated 24 volt and regulated 14 volt DC power. The regulated 14Vdc power is appropriate for most small telemetry radios and other "12 volt" battery compatible equipment in addition to the ICL controllers and RTUs.
With the UPS option, the regulated output is battery-backed when AC power is lost. An additional 24Vdc supply is also made available, with the UPS option, for battery-backed analog loop power. Backup power is provided by a separate "gel-cell" battery (purchased separately) that the UPS option charges and keeps charged with a 2-stage "float" charger.
The UPS option utilizes a microprocessor with communications capabilities to access internal power supply information including voltage levels, charging status, battery condition and alarm information via an RS-232 serial port. Alarm information is also available via a pair of alarm "contacts".
| Total DC Power | 36 watts (without UPS option), 33 watts (with UPS option) Total power draw summed between all DC outputs must not exceed this value: Total DC Power = (V 1 x I 1 ) + (V 2 x I 2 ) + [(V 3 x I 3 ) if UPS option] |
| DC Output #1 | 17 to 24Vdc @ 1.6A maximum |
| DC Output #2 | 14Vdc @ 2.5A maximum |
| DC Output #3 | 24Vdc @ 0.5A maximum (available with UPS option only) |
| AC/DC Input Power | 90 to 134Vac, 1.0A maximum, 47Hz to 63Hz, or 180 to 264Vac, 0.5A maximum, 47Hz to 63Hz, or 17 to 28Vdc, 2.5A maximum (external fusing required) |
| Charger type | 2-stage float (constant current, then constant voltage float) |
| Charging current | Current limited to 0.15A |
| Battery Test Interval | Once per minute or once every 5 seconds, DIP switch selectable by user |
| Battery Protection | 5A self-resetting fuse |
| Communications | RS-232, TXD (Transmit Data) only, 9600 baud, no parity, 8 data bits, 1 stop bit |
| Message data | DC input voltage, Battery Charging Voltage, Battery Voltage under load test +14 volt regulated output voltage, +24 volt regulated output voltage Alarms (power fail, +24 current limit, low battery, battery cutoff status) |
| Alarm Outputs | Quantity 2 -- Alarm and Low Battery, optically isolated FET "contact closure" (NC) |
| Alarm Contact Rating | 350Vrms, 0.1A maximum |
| Operating Temperature | -40°C to +80°C |
| Humidity | 0 to 95%, non-condensing |
| Enclosure Material | Polycarbonate, UL 94V-2 |
| Enclosure Mounting | 35mm DIN rail or Direct Panel Mounting with two #8 screws |
| Dimensions | 75 x 100 x 110 mm 2.95 x 3.95 x 4.33 inches |
| Terminal Block Type | Removable, screw-clamp terminals, 300V, 10A maximum, #22 to #14 AWG |
| Model # | Description |
| ICL-4003 | 36 Watt Power Supply (no UPS Option) |
| ICL-4003-UPS | 36 Watt Uninterruptible Power Supply (with UPS Option) |
|
|
|
|
|
|