| Features | Selection Guide | Specifications | DataSheet | Technical Manual |
|
|
Selection Guide |
Back to Top |
MAXIO™ Type |
Discrete In |
Discrete Out |
Analog In |
Analog Out |
MaxIO D24/16 * |
24 | 16 (Relay) | - | - |
MaxIO U16/6 ** |
- | - | 16 | 6 |
* "D" stands for Discrete Input and Output
** "U" stands for Universal Input
MAXIO™ distributed I/O modules can significantly reduce system costs by eliminating long runs of field wiring, reducing the size of electrical panels, reducing startup and maintenance time.
MAXIO™ support RS-485 links up to 1 mile over low-cost twisted pair wiring,
and RS-232 links for local connections to PC computers and equipment, as well
as modem interfaces to data radios, leased telephone lines or fiber optic cable.
A single network over any media is expandable to 8,000 I/O points.
Specifications |
Back to Top |
| MAXIO™ Discrete Input(61-00xx, 61-02xx) Datasheet | |
| Quantity/Type of Discrete Input | 24 |
| Input Voltage, Nominal | 12/24 Vdc/Vac (61-00xx), 120 Vdc/Vac (61-02xx) |
| Input Operating Range | 0 to 60 Vdc/Vac (61-00xx), 0 to 125 Vdc/Vac (61-02xx) |
| Input Overvoltage Tolerance | 140 Vdc/Vac (61-00xx), 190 Vdc/Vac (61-02xx) |
| Input Resistance, Typical | 10,000 ohms (61-00xx), 100,000 ohms (61-02xx) |
| Input Noise Filtering, AC/DC | 20Hz/40Hz (DI 1 thru 4 with filters on) |
| Counting Frequency, DC (DI 1 thru 4) | Greater than 5kHz (DI 1 thru 4 with filters off) |
| Counting Frequency, AC/DC (all inputs) | 10Hz/40Hz (DI 1 thru 4 with filters on) |
| MAXIO™ Discrete Output(61-00xx, 61-02xx) Datasheet | |
| Quantity of Discrete Outputs | 16 |
| Output Type, Configuration | Relay (form A) |
| Output Operating Current/Voltage Range | 10A @ 120Vac, 5A @ 30Vdc |
| Contact Protection | Internal RC Snubber |
| Flash ON/OFF Times/Resolution | 0 to 2.55 sec., 10ms increments |
| MAXIO™ Universal Inputs (61-10xx) Datasheet | |
| Quantity of Analog Inputs | 16 (61-10xx) |
| Universal Input Types | Current 20mA ( 0mA to 46mA) Voltage 5Vdc (0Vdc to 5.625Vdc) +/-300mV (-300mV to +300mV) Resistance 65,000 ohms (0 to 65,535 ohms) Thermocouple Type J (-240.7 to 1199.0 degrees C) Type K (-261.2 to 1369.5 degrees C) Type T (-263.2 to 398.8 degrees C) Type E (-267.4 to 999.0 degrees C) Type R (-43.1 to 1759.8 degrees C) Type S (-41.3 to 1759.1 degrees C) Type B (-253.4 to 1792.1 degrees C) Type N (-255.4 to 1296.8 degrees C) Thermistor 10K Ohm - II (-401 to 173.9 degrees C) 10K Ohm - III (-401 to 188.0 degrees C) RTD 100 Ohm - 385 (-198.9 to 869.4 degrees C) 100 Ohm - 392 (-200.0 to 629.7 degrees C) 1K Ohm - 385 (-198.9 to 869.4 degrees C) Discrete Input TTL Level Dry Contact |
| Resolution | 16 bits (1 part in 65,535) |
| Input Overload Tolerance | Input voltage limiting starts a 6Vdc Input current limited to 50mA |
| Overload / Transient Protection | Transorb & Self Resetting Polyfuse |
| Coversion Rate | Approx. 2 samples/sec. per point |
| Noise Rejection (50/60Hz) | -120 dB |
| MAXIO™ Analog Output (61-10xx) Datasheet | |
| Quantity of Discrete Outputs | 6 |
| Output Type, Configuration | 0 or 4 to 20mA (0 to 21mA) |
| Converter Type | High-frequency PWM |
| Resolution | 12 bits (1 part in 4096) |
| Maximum Load Resistance | 250 ohms @ 10Vdc loop power 500 ohms @ 15Vdc loop power 750 ohms @ 20Vdc loop power 1000 ohms @ 25Vdc loop power |
| MAXIO™ Communications - All Modules | |
| Serial Ports | 1, Isolated RS-232 and RS-485, 1 RS-232 Radio / Modem Diagnostic port |
| Data Rate | 2400 baud to 115K baud |
| Communications Protocols | Modbus RTU / Bricknet (Auto-sensing) |
| MAXIO™ General Specifications - All Modules | |
| Dimensions | 7.0 W x 6.0 L x 2.5 D (178mm x 152mm x 64mm) |
| Power (Input Voltage Range) | 8 to 26Vac, 10 to 36Vdc |
| Sensor Power Supply | 7 to 32Vdc, 0.75A maximum |
| Temperature, operating | -40°C to 75°C (-40°F to 167°F) |
| Temperature, storage | -40°C to 100°C (-40°F to 212°F) |
| Isolation, Field to Logic | 2,000 volts |
| Humidity | 5 to 85% RH (non-condensing) |
| Wiring Terminations | Removable Terminal Blocks #14 to #26 stranded, #12 solid |
Download Datasheet: |
Back to Top |
Distributed I/O Module Datasheet |
|
|
|
|
|
* PDF format -- requires Adobe Acrobat Reader 4.0 or newer.
* Click below to get it for free.
*